Step
In Wireless Builder, set transmitter's Write Lock to Unlocked.
1
In Wireless Builder, set the transmitter's channel to OOS (Out of Service).
2
Loosen the M3 locking set screw on the transmitter's battery end-cap (opposite end from
3
display). Unscrew and remove the end cap.
See Figure 2 for terminal connections. If your process input is connected to the channel,
4
disconnect it first, then connect a calibrator source to the channel's terminals. It is not
necessary to disconnect any jumper wires on the terminals.
Select USER CAL by scrolling through menu. Follow displayed instructions.
5
Using your calibration source, apply the low calibration value indicated on display.
Press Enter to accept the value. Display will say BUSY, then CAL LO COMPLETE.
Press Enter to continue.
Apply the high calibration input value indicated on display.
Press Enter to accept the value. Display will say BUSY, then SUCCESS.
If calibration is unsuccessful at any of steps mentioned above an error message is displayed.
See Table 2.
Press Enter to return to PV display.
Exit the menu.
6
Reverse steps 3 and 4.
7
When ready, in Wireless Builder return the transmitter's channel to service and set Write Lock
8
to Locked.
4
4
1
1
5
5
2
2
6
6
3
3
Revision 9
July 2011

Table 1 User calibration

+
+
+
+
0-5V
0-5V
1-5V
1-5V
-
-
-
-

Figure 2 Calibration wiring: voltage (left), current (right)

OneWireless XYR 6000 HLAI Transmitter R120 User's Manual
3.4. Calibrating the transmitter
Action
+
+
0-20 mA
0-20 mA
0-20 mA
4-20mA
4-20mA
4-20mA
-
-