3.1
Installation
Refer to the XYR 6000 Transmitter Quick Start Guide (document 34-XY-25-21) for installation, mounting
and wiring of your XYR 6000 transmitter.
3.2
Configuration
The XYR 6000 Transmitter contains the electronics interface compatible for connecting to the
OneWireless network. An operator uses the Wireless Builder application to configure blocks and to
change operating parameters. These changes are written to the transmitter when it is authenticated by a
security key.
3.3
Connecting to network
Use Authentication Device to connect your transmitter to the OneWireless network. See page 30.
3.4
Calibrating the transmitter
Methods of calibration
Calibration can be done at the transmitter or at Wireless Builder's Method Manager. For all calibration
methods at the transmitter, Wireless Builder must be used to unlock and take the channel out of service.
For the STTW401, calibration applies only to the thermocouple/millivolt input, not to the discrete inputs.
•
User calibration - Calibrates the channel to the low and high range values for the selected channel's
input type.
•
Restore calibration - Calibration constants for the selected channel are restored to factory defaults.
•
Clear calibration - Factory or user calibration constants for the selected channel are cleared.
Additional calibration commands are available in Wireless Builder.
Rev. 3
OneWireless XYR 6000 Temperature and Temperature/Discrete Input Transmitter User's Manual
6/24/08
3. Preparation
3. Preparation
3.1. Installation