3. Preparation

3.1. Installation

3.1
Installation
Refer to the XYR 6000 Transmitter Quick Start Guide (document 34-XY-25-21) for installation, mounting
and wiring of your XYR 6000 transmitter.
3.2

Configuration

The XYR 6000 Transmitter contains the electronics interface compatible for connecting to the
OneWireless network. An operator uses the Wireless Builder application to configure blocks, to change
operating parameters, and to create linkages between blocks that make up the transmitter's configuration.
These changes are written to the transmitter when it is authenticated by a security key.
3.3

Connecting to network

Use Authentication Device to connect your transmitter to the OneWireless network. See page 23.
3.4

Calibrating the transmitter

Overview

For all calibration methods, Wireless Builder must be used to unlock and take the channel out of service.
You can set the zero offset at the transmitter by use of the infrared port. Additional calibration commands
such as upper and lower trim are available in Wireless Builder.

Calibrate zero

Calibrates the sensor to correct the input measurement due to fill fluid and transmitter position effects once
the transmitter is installed and operating under process conditions.
ATTENTION
Setting user trim points will effectively override the calibration zero. Normally
the calibration zero is only required if you do not intend to provide process-
specific trim points.
10
3. Preparation
OneWireless XYR 6000 Pressure Transmitter R120 User's Manual
Revision 8
November 2010