Utilizing Panel (Leds And Keys) By Communication; Led Setting By Communication - Toshiba Tosvert VF-S15 Series Instruction Manual

Rs485 communication function
Hide thumbs Also See for Tosvert VF-S15 Series:
Table of Contents

Advertisement

8.3.Utilizing panel (LEDs and keys) by communication

The VF-S15 can display data that is not related to the inverters through an external controller or
other means. Input by key operations can also be executed. The use of inverter resources re-
duces the cost for the entire system.

8.3.1. LED setting by communication

Desired
<How to Set>
Set the standard monitor display selection parameter to "communication LED setting
( f710 = 18 )."
When in the standard monitor mode status, LED information is displayed according to the setting of
Communication Number FA65.
" data " in shipment setting)
In case of an alarm while setting communication LEDs, the alarm display will alternately display
specified LED data and alarm message.
For example, if an over-current alarm (alarm display " c ") occurs while " 60 . 0 " is displayed by this
function, " c " and " 60 . 0 " will be displayed alternately.
Commu-
nication
Number.
FA65
Select display by communication
FA66
Numeric display data
(Enabled if FA65=0)
FA67
Decimal point position
(Enabled if FA65=0)
FA68
LED data 0 for unit
(Enabled if FA65=0)
FA70
ASCII display data 1, first digit from left
(Enabled if FA65=1)
FA71
ASCII display data 1, second digit from left
(Enabled if FA65=1)
FA72
ASCII display data 1, third digit from left
(Enabled if FA65=1)
FA73
ASCII display data 1, fourth digit from left
(Enabled if FA65=1)
FA74
LED data 1 for unit
(Enabled if FA65=1)
FA75
ASCII display data 2, first digit from left
(Enabled if FA65=2)
FA76
ASCII display data 2, second digit from left
(Enabled if FA65=2)
FA77
ASCII display data 2, third digit from left
(Enabled if FA65=2)
FA78
ASCII display data 2, fourth digit from left
(Enabled if FA65=2)
FA79
LED data 2 for unit
(Enabled if FA65=2)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
LED information can be displayed by communication.
Parameter Name
(Set to Communication Number FA65 = 1 and initial data
0: Numeric data (FA66, FA67, FA68)
1: ASCII data 1 (FA70, FA71, FA72, FA73,
FA74)
2: ASCII data 2 (FA75, FA76, FA77, FA78,
FA79)
0-9999
0: No decimal point (xxxx)
1: First digit below decimal point (xxx.x)
2: Second digit below decimal point (xx.xx)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0 – 127 [0 – 7FH]
(See ASCII LED display code chart)
0 – 256 [0 – FFH]
(See ASCII LED display code chart)
0 – 256 [0 – FFH]
(See ASCII LED display code chart)
0 – 127 [0 – 7FH]
(See ASCII LED display code chart)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0 – 127 [0 – 7FH]
(See ASCII LED display code chart)
0 – 256 [0 – FFH]
(See ASCII LED display code chart)
0 – 256 [0 – FFH]
(See ASCII LED display code chart))
0 – 127 [0 – 7FH]
(See ASCII LED display code chart)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
63
E6581913
Range
Shipment
setting
1
0
0
0
100 [64H]
(' d ')
65 [41H]
(' a ')
116 [74H]
(' t ')
65 [41H]
(' a ')
0
48 [30H]
(' 0 ')
48 [30H]
(' 0 ')
48 [30H]
(' 0 ')
48 [30H]
(' 0 ')
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents