Advertisement

8.3.2.Key utilization by communication

The VF-S15 can use the panel keys on the inverters through external communication.
 Key Monitoring Procedure
Set panel key selection (Communication Number: FA10) to "1" to set the external key mode.
However, if communication duration is less than 1sec to avoid an inverter operation shutdown in
communication disruption, communication must always be maintained, such as monitoring key data
and LED data to automatically reset inverter operations to inverter key operation (FA10 = 0). Set
to the external communication key mode (FA10 = 1) to disable the key function of the inverters so
that inverter operation will not be affected by pressing of the keys on the inverters. By monitoring
key information, which is input by the keys on the inverters in this condition, through inverter key
data (Communication Number; FC01), the keys on the inverters can be operated through a control-
ler and other devices.
* When the key mode is the external key mode, key operation as an inverter function is disabled
and the inverters cannot be stopped by pressing the STOP key to stop inverter operation. Enable
emergency stop through an external terminal or other device when an inverter stop is desired.
Panel Key Selection (Communication Number: FA10)
The panel key selection parameter (Communication Number; FA10) discriminates which keys are to be used, panel keys
on the inverters or keys sent by external communication, as panel keys used in panel processing of the inverters.
Communication No.:FC01
Panel key data of invert-
ers
Communication No.:FA11
External
key data
Keys on inverters enabled (Communication Number; FA10 = 0):
Key data: Data of keys on inverters (Communication Number: FC01)
Bit15 Bit14-Bit9
-
-
External keys enabled (Communication Number; FA10 = 1):
Key data: External key data (Communication Number: FA11)
Bit15 Bit14-Bit9
-
-
Key monitoring (Communication Number: FC00): *Bit15 is always 1.
Bit15 Bit14-Bit9
-
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
communication
Bit8
Bit7
Bit6
-
-
EASY
Bit8
Bit7
Bit6
-
LOC/
EASY
REM
Bit8
Bit7
Bit6
-
LOC/
EASY
REM
FA10="0"
Communication No.:FC00
Key data for inverter con-
trol panel processing
FA10="1"
Bit5
Bit4
Bit3
ENT
MODE
DOWN
Bit5
Bit4
Bit3
ENT
MODE
DOWN
Bit5
Bit4
Bit3
ENT
MODE
DOWN
66
E6581913
Bit2
Bit1
Bit0
UP
STOP
RUN
Bit2
Bit1
Bit0
UP
STOP
RUN
Bit2
Bit1
Bit0
UP
STOP
RUN