2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type
number is returned to the computer in addition to the checksum. At time of broadcast communica-
tion of the binary mode, returning of data is not executed except for the inverter to be returned (in-
verter number 00H) and when the inverter number is not matched. This is because there will be a
risk that the returned data may be deformed.
(3.5bytes
Blank)
Norn (1 byte)
Data (2 bytes)
 Examples:
2FH, 4EH, 00H, 00H, 7DH ... Impossible to execute (e.g., a change of maximum frequency data
2FH, 4EH, 00H, 01H, 7EH ... Data setting error (The data specified falls outside the specified
2FH, 4EH, 00H, 02H, 7FH ... No communication number (There is no communication number that
2FH, 4EH, 00H, 04H, 81H ... Checksum error (The checksum result differs.)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Omissible
"/"
INV-NO
Norn
(2FH)
1 byte
(4EH)(6EH)
Checksum area
: Communication error command ... This command is also used for a check when the in-
verter is tripped.
"4EH (N)" is returned under normal conditions, while "6EH (n)" is returned when the in-
verter is tripped.
: Error code (0000~0004)
0000 ... Impossible to execute (Although communication is established normally, the
command cannot be executed because it is to write data into a parameter whose
setting cannot be changed during operation (e.g., maximum frequency) or the
EEPROM is faulty.)
0001 ... Data error (The data is outside the specified range or it is composed of too many
digits.)
0002 ... Communication number error (There is no communication number that matches.)
0004 ... Checksum error (The checksum result differs.)
No code returned ...Command error, format error (parity, overrun or framing error) or the
inverter number does not match or an inverter in broadcast communi-
cation in the binary mode except for the inverter for data returning (the
inverter numbered 00H).
during operation)
range.)
matches.)
DATA
2 bytes
Not omissible
12
E6581913
SUM
(3.5bytes
1 byte
Blank)