8.4. Utilizing panel (LEDs and keys) by communication

The VF-S11 can display data that is not related to the inverters through an external controller or other
means. Input by key operations can also be executed. The use of inverter resources reduces the
cost for the entire system.

8.4.1. LED setting by communication

Desired
<How to Set>
Set the standard monitor display selection parameter to "communication LED setting (  =  )."
When in the standard monitor mode status, LED information is displayed according to the setting of
Communication Number FA65. (Is set to Communication Number FA65 = 1 and initial data "dAtA"
in shipment setting)
In case of an alarm while setting communication LEDs, the alarm display will alternately display
specified LED data and alarm message.
For example, if an over-current alarm (alarm display "  ") occurs while "  .  " is displayed by this
function, "  " and "  .  " will be displayed alternately.
Commu-
nication
Number.
FA65
Select display by communication
FA66
Numeric display data
(Enabled if FA65=0)
FA67
Decimal point position
(Enabled if FA65=0)
FA68
LED data 0 for unit
(Enabled if FA65=0)
FA70
ASCII display data 1, first digit from
left
(Enabled if FA65=1)
FA71
ASCII display data 1, second digit
from left
(Enabled if FA65=0)
FA72
ASCII display data 1, third digit from
left
(Enabled if FA65=1)
FA73
ASCII display data 1, fourth digit from
left
(Enabled if FA65=1)
FA74
LED data 1 for unit
(Enabled if FA65=1)
FA75
ASCII display data 2, first digit from
left
(Enabled if FA65=2)
FA76
ASCII display data 2, second digit
from left
(Enabled if FA65=2)
FA77
ASCII display data 2, third digit from
left
(Enabled if FA65=2)
FA78
ASCII display data 2, fourth digit from
left
(Enabled if FA65=2)
FA79
LED data 2 for unit
(Enabled if FA65=2)
LED information can be displayed by communication.
Parameter Name
Range
0: Numeric data (FA66, FA67, FA68)
1: ASCII data 1 (FA70, FA71, FA72, FA73,
FA74)
2: ASCII data 2 (FA75, FA76, FA77, FA78,
FA79)
0-9999
0: No decimal point (xxxx)
1: First digit below decimal point (xxx.x)
2: Second digit below decimal point (xx.xx)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart))
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
56
E6581222
Shipment
setting
1
0
0
0
64H ('d')
41H ('A')
74H ('t')
41H ('A')
0
30H ('0')
30H ('0')
30H ('0')
30H ('0')
0