Write Command (06H, 10H) - Toshiba Tosvert VF-S15 Series Instruction Manual

Rs485 communication function
Hide thumbs Also See for Tosvert VF-S15 Series:
Table of Contents

Advertisement

5.1.4. Write command (06H, 10H)

 Do not write the same parameter to the EEPROM more than 10,000 times. The life time of EEPROM is
approximately 10,000 times. (Some parameters are not limited, please refer to the "9. Parameter data")
Mandatory
action
5.1.4.1. Write command (06)
 Computer → Inverter *The text size is 8 bytes fixed.
Inverter
Command
No.
06
1) Inverter No. (1 byte)
2) Command (1 byte)
3) Communication No. (2 bytes) : Set in the order of high to low numbers.
4) Write data (2 bytes)
5) CRC16 (2 bytes)
 Inverter → Computer (Normal return) *The text size is 8 bytes fixed.
Note: The return packet and the sending packet are same.
Inverter
Command
No.
06
 Inverter → Computer (Abnormal return) *The text size is 5 bytes fixed.
Inverter
Command Error Code
No.
86
1) Inverter No (1 byte)
2) Command (1 byte)
3) Error code (1 byte)
4) CRC16 (2 bytes)
 Example: Writing in frequency command value (FA01) (60Hz)
(Computer → inverter)
(Inverter → computer)
 Example: Communication number error
(Computer → inverter)
(Inverter → computer)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
CAUTION
Communication No.
high
low
: ---
: Set the write command (06H fixed).
: Set in the order of high to low write data.
: ---
Communication No.
high
low
CRC16
low
high
: ---
: 86H fixed (Read command error) (Command + 80H)
: See "5.3. Error codes".
: ---
01 06 FA 01 17 70 E6 C6
01 06 FA 01 17 70 E6 C6
01 06 FF FF 00 00 89 EE
01 86 02 C3 A1
Write Data
high
low
low
Write Data
high
low
low
31
E6581913
CRC16
high
CRC16
high