WEG CFW09 Quick Start Manual page 6

Vectrue technology
Hide thumbs Also See for CFW09:

Advertisement

Parameters Example:
Inverter Data (Example)
Line: CFW09
Rated Current: 9 A
Rated Voltage: 380...480 V
Model: CFW090009TGZ
The following is a typical list of parameter changes needed using the Motor/Inverter data shown above and the
factory 60Hz default setting (P204=5).
P000=5
P204=5
P201=1
P296=3
P400=460
P401=7.9
P403=60
P402=1730
P404=8
P406=0
P202=0
P100=20
P101=20
P133=90
P134=1730
P205=2
Local/Remote parameters allow the inverter to be set up to operate from Keypad, Remote Terminal, or a
programmed combination of keypad and terminal inputs.
P220 – Local/Remote Selection
P221 – Local Speed Reference Selection
P222 – Remote Speed Reference Selection
P223 – Local FWD/REV Selection
P224 – Local Start/Stop Selection
P225 – Local Jog Selection
P226 – Remote FWD/REV Selection
P227 – Remote Start/Stop Selection
P228 – Remote Jog Selection
Read Only Parameters (P001 – P065) can be used for monitoring and troubleshooting. For a full list and
description please read the CFW09 User's Guide. By monitoring certain read only parameters, the status of
inputs, outputs, and drive operational values can be determined without the use of any other test equipment.
P001 – Speed Reference
P003 – Motor Current
P004 - used to monitor DC Bus Voltage.
P005 – Motor Frequency
P006 – Inverter Status
P012 (Digital Input Status) – used to monitor digital inputs.
P013 (Relay Output Status) – used to monitor relay outputs.
P014 to P017 and P060 to P065 – used to read the last 10 faults.
P018 to P021 – used to read analog inputs
These are just a few examples of inverter set-up and parameters. Please read the CFW09 User's Guide for
additional information.
Motor Data (Example)
Power: 5 HP
Rated Speed: 1730 RPM, 4 Pole
Rated Current: 7.9 A
Rated Voltage: 460 V
Frequency: 60 Hz
Cooling: Self-ventilated
Parameter Access (5 = Password)
Loads Factory Default (5 = 60Hz Default) (P204=7 or 8 saves the user's data)
Language Setting (1 = English)
Inverter Rated Voltage (3 = 440-460V)
Motor Rated Voltage = 460V
Motor Rated Current = 7.9A
Motor Rated Frequency = 60Hz
Motor Rated RPM = 1730
Motor Rated HP = 5HP
Motor Ventilation Type (0=Self Ventilated)
Type of Control = V/F 60Hz
Acceleration Time = 20 seconds
Deceleration Time = 20 seconds
Minimum Speed = 90 RPM
Maximum Speed – 1730 RPM
Display Default = Motor Speed