ABB REM 610 Operator's Manual page 44

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
REM 610
44
Motor Protection Relay
Operator's Manual - ANSI version
Table 4.3.2.3.-1
IRF codes (Continued)
Fault code
a)
51, 52, 53
, 54, 56
55
75
80
81
82
85
86
90
95
104
131, 139, 195, 203, 222, 223 Internal reference voltage error
253
a)
All setting values will be zero during the fault
b)
May be corrected by formatting to the factory setting.
Warning
In case of a less severe fault (warning), the relay continues to operate except for
those protection functions possibly affected by the fault. At this type of fault, the
green target LED remains lit as during normal operation, but the text WARNING
with a fault code or a text message indicating the fault type replaces the name of the
feeder on the display in the idle mode. Some of these faults can be corrected by a
relay operator at site. After the fault has disappeared or been corrected, the message
is automatically cleared.
WARNING
BATTERY LOW
Fig. 4.3.2.3.-2
Warning with text message
If more than one type of fault occur at the same time, one single numeric code which
indicates all the faults is displayed. For instance, 2049 implies two faults: the
battery is low and the temperature sensor RTD6 is faulty. The code is composed of
the weighting factors assigned to each fault type as follows: 1 + 2048; see
Table 4.3.2.3.-2
Type of fault
b)
Faulty parameter memory
Faulty parameter memory, calibration parameters
RTD module faulty
RTD module missing
RTD module unknown
RTD module configuration error
Power supply module faulty
Power supply module unknown
Hardware configuration error
Communication module unknown
Faulty configuration set for IEC 60870-5-103
Error in the measuring unit
1MRS755538
A040279

Advertisement

Table of Contents
loading