Motor Protection Relay
Operator's Manual - ANSI version
Two change-over (form c) non-trip contacts
*
Output contact functions freely configurable for wanted operation
*
Two galvanically isolated digital inputs and three additional galvanically isolated
*
digital inputs on the optional RTD module
Disturbance recorder:
*
Recording time up to 80 seconds
*
Triggering by one or several internal or digital input signals
*
Records four analog channels and up to eight user-selectable digital channels
*
Adjustable sampling rate
*
Non-volatile memory for:
*
Up to 100 event codes with time stamp
*
Setting values
*
Disturbance recorder data
*
Recorded data of the five last events with time stamp
*
Number of AR shots and pickups/trips for protection elements
*
Operation target messages and LEDs showing the status at the moment of
*
power failure
Multi-language support
*
User-selectable password protection for the HMI
*
Display of primary current values
*
Demand values
*
All settings can be modified with a PC
*
Optical front communication connection: wirelessly or via cable
*
Optional rear communication module with plastic fibre-optic, combined fibre-
*
optic (plastic and glass) or RS-485 connection for system communication using
the SPA-bus, IEC 60870-5-103 or Modbus (RTU and ASCII) communication
protocol
Battery back-up for real-time clock
*
Battery charge supervision
*
Continuous self-supervision of electronics and software
*
Detachable plug-in unit
*
1MRS755538