Vacon 100 - Technical Data - Vacon 100 Installation Manual

Hvac drives
Hide thumbs Also See for 100:
Table of Contents

Advertisement

vacon • 78
7.2

Vacon 100 - technical data

Mains connection
Motor connection
Control characteristics
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 31. Vacon 100 technical data
Input voltage U
in
Input frequency
Connection to mains
Starting delay
Output voltage
Continuous output cur-
rent
Output frequency
Frequency resolution
Switching frequency
(see parameter
P3.1.2.1)
Frequency reference
Analogue input
Panel reference
Field weakening point
Acceleration time
Deceleration time
208...240 V; 380...480 V; -10%...+10%
50...60 Hz -5...+10%
Once per minute or less
6 s (MR4 to MR6); 8 s (MR7 to MR9)
0-U
in
I
:Ambient temperature max. +40 °C, up to
L
+50 °C with derating; overload 1.1 x I
10 min.)
0...320 Hz (standard)
0.01 Hz
MR4-6: 1.5...10 kHz;
Defaults:
MR4-6: 6 kHz (except 0012 2, 0031 2, 0062 2,
0012 4, 0031 4 and 0061 4: 4 kHz)
MR7-9: 1.5...6 kHz;
Defaults:
MR7: 4 kHz
MR8: 3 kHz
MR9: 2 kHz
Automatic switching frequency derating in
case of overload.
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
8...320 Hz
0.1...3000 sec
0.1...3000 sec
Technical data
(1 min./
L