Installation with barriers
When installing the Emerson 781 in a hazardous area there are two I.S. barriers
that need to be installed: a power barrier and a signal barrier. The signal and the
power are two separate I.S. circuits so they must comply with proper I.S.
segregation distance. When using the Emerson recommended barriers the
input power of the Gateway should be 20–30 VDC, with current capacity of at
least 330 mA.
The signal barrier needs additional power. You can wire it to the Emerson 1410D
terminals or to a separate power supply. Make sure power supply is rated to
handle power drawn for the barrier.
variations of powering the signal barrier.
Figure 10. Emerson 1410D and 781 with Gateway Powered Barrier
A. Emerson Wireless 1410D Gateway
B. Attach shield pair cable (Belden 3084A)
C. Tape back shield wire and foils
D. Short these terminals for 250 Ω
14