Installation of WL2/WN2 option
1. Mount the antenna on a 1
equipment.
2. Connect the lightning arrestor either to the electrical cabinet or directly
outside the wall or right outside the wall (depending on where the Gateway is
located).
3. Install the grounding lug, lock washer, and nut on top of the lightning
arrestor.
4. Bond the grounding terminal of the lightning arrestor to a common earth
point using individual high integrity, low resistance means as shown in
Figure
5. The DIN rail cabinet must be grounded as well. A #6 AWG (or 4.11 mm
European) copper wire bonding conductor with the shortest length possible,
no sharp bends, and no coiling is recommended.
6. All the outdoor connections should be made hand tight plus an
a wrench and wrapped with the coaxial seal (shown in
7. Ensure the mounting mast, lightning arrestor, and Gateway are grounded
according to local/national electrical code.
Any spare lengths of coaxial cable should be placed in 1 ft. (0.3 m) coils.