Emerson 1410 A/B Quick Start Manual page 13

Wireless and gateway with781 field link
Table of Contents

Advertisement

May 2018
Installation without barriers
A shielded twisted pair cable is needed for connecting the Emerson 1410D and
781 (refer to
from the Emerson 1410D.
Figure 9. Emerson 1410D and 781 without Barriers Installation
Gray line means internal
connection
Data A (+)
A. Emerson Wireless 1410D Gateway
B. Attach shield pair cable (Belden 3084A
or equivalent)
C. Tape back shield wire and foils
Figure
9). The Emerson 781 can be located up to 656 ft. (200m)
10.5-30VDC
Red
Blk
Wht
B
C
Blu
Wht
D
Data B (-)
A
Blu
Red
Blk
Return (-)
24 VDC (+)
E
D. Short these terminals to enable 250 Ω
terminating resistor
E. Emerson Wireless 781 Field Link
Quick Start Guide
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1410 d

Table of Contents