12.2.6 - Brine option (Options 5B and 6B)
The 5B medium-temperature brine solution option is used to
produce low temperature chilled water down to 0°C.
Production of brine solution from 0°C to -15°C is only possible
with the 6B low-temperature brine solution.
The unit is equipped with insulation on the intake tubes. The
insulation is reinforced on the low-temperature brine solution
option.
Operating range
Low-temperature brine solution
30RBM 160-400 and 30RBP 160-400
Low-temperature Propylene Glycol
50
48
45
40
35
31
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
-15 -14 -13 -12 -11 -10 -9
-8
Brine solution mix type heat exchanger leaving water temperature (°C)
Medium-temperature brine solution
30RBM 160-520 and 30RBP 160-520
Medium-temperature Ethylene and Propylene Glycol
50
48
45
43
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
-2
-1
0
Brine solution mix type heat exchanger leaving water temperature (°C)
54
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
1
2
3
4
The operating range depends on:
the size of the unit,
the glycol type,
its concentration,
the flow rate,
the temperature of the glycol solution,
the condensation pressure (ambient temperature).
50
48
45
40
35
30
28
25
20
15
10
5
0
-5
-10
-15
-20
-25
-20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0
5
6
Brine solution type heat exchanger leaving water temperature (°C)
NOTES
-
-
Legend
Operating range for 30RBM or 30RBP brine solution unit
Operating range for 30RBM unit equipped with options 28B and 28C (winter
operation). Options 28B-28C (with two-speed lead fan for each circuit) allows
operation down to -10 °C outside temperature.
RBP operating range or extension of the operating range, 30RBM unit
equipped with option 28. Option 28 (with variable-speed lead fan for each
circuit) allows operation down to -20°C outside temperature.
5
6
30RBM 160-400 and 30RBP 160-400
Low-temperature Ethylene Glycol
Evaporator ∆T = 5K max
These operating ranges are guidelines only. Verify the operating range with the
Carrier electronic catalogue.