13.10 - Refrigerant properties

Properties of R410A
Saturated Temp.
Pressure gauge
-20
297
-19
312
-18
328
-17
345
-16
361
-15
379
-14
397
-13
415
434
-12
-11
453
-10
473
-9
493
-8
514
-7
535
-6
557
-5
579
-4
602
-3
626
-2
650
-1
674
0
700
1
726
2
752
3
779

13.11 - Power factor correction

The check involves measuring the input current of each capacitor battery. The check must be carried out using a true RMS
meter reading:
Check per phase current delivered by each capacitor and compare it to nominal values. In case of capacitance losses or
unbalance, the capacitors must be replaced.
Make sure the current through the capacitor does not exceed 1.3 x Ir. A higher value may indicate a strong presence of
harmonics, which will impact the lifetime of the capacitor.
The absence of current despite the capacitor being energized indicates a fault. This defect is confirmed by removing the
capacitors and checking the underside.
64
Saturated temperatures based on the gauge pressure (in kPag)
Saturated Temp.
Pressure gauge
4
807
5
835
6
864
7
894
8
924
9
956
10
987
11
1020
1053
12
13
1087
14
1121
15
1156
16
1192
17
1229
18
1267
19
1305
20
1344
21
1384
22
1425
23
1467
24
1509
26
1596
25
1552
27
1641
Faulty
Saturated Temp.
Pressure gauge
28
1687
29
1734
30
1781
31
1830
32
1880
33
1930
34
1981
35
2034
2087
36
37
2142
38
2197
39
2253
40
2311
41
2369
42
2429
43
2490
44
2551
45
2614
46
2678
47
2744
48
2810
49
2878
50
2947
51
3017
Correct
Saturated Temp.
Pressure gauge
52
3088
53
3161
54
3234
55
3310
56
3386
57
3464
58
3543
59
3624
60
3706
61
3789
62
3874
63
3961
64
4049
65
4138
66
4229
67
4322
68
4416
69
4512
70
4610