Acyclic MRP Group 1 Data – Subslot 2
Byte
Name
0
MRP Mode
1
MRP Role
2
Ring Port1 of MRP
3
Ring Port2 of MRP
Acyclic MRP Group 2 Data – Subslot 3
Byte
Name
0
MRP Mode
1
MRP Role
2
Ring Port1 of MRP
3
Ring Port2 of MRP
GFK-3030
Access
Value
Output Description
read-write
0
Disable MRP
1
Enable MRP (Default)
read-write
0
MRC (Default)
1
MRM
Assigned Port ID of Ring Port1
read-write
0~7
(0 corresponds to Port 1,
7 corresponds to Port 8)
0 is default value.
read-write
0~7
Assigned Port ID of Ring Port 2
(0 corresponds to Port 1,
7 corresponds to Port 8)
1 is default value.
Access
Value
Output Description
read-write
0
Disable MRP (Default)
1
Enable MRP
read-write
0
MRC (Default)
1
MRM
read-write
0~7
Assigned Port ID of Ring Port1
(0 corresponds to Port 1,
7 corresponds to Port 8)
2 is default value.
read-write
0~7
Assigned Port ID of Ring Port 2
(0 corresponds to Port 1,
7 corresponds to Port 8)
3 is default value.
December 2017
Chapter 4. Configuration
Input Description
MRP Disabled
MRP Enabled
MRC
MRM
Port ID
Port ID
Input Description
MRP Disabled
MRP Enabled
MRC
MRM
Port ID
Port ID