Toshiba G7 Quick Start Manual page 58

G7 adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

MCP
Model
Rating
VT130G7U
(Amps)
Recommended
6015B
15
6025B
15
6035B
15
6060B
15
6080B
15
6120B
30
6160B
30
6220B
50
6270B
50
6330B
50
6400B
75
6500B
100
6600B
100
6750B
125
610KB
150
612KB
200
615KB
250
620KB
300
625KB
400
630KB
500
Note:
Input and Output power wire requires shielding for CE compliance.
Note:
(*) Indicates that the item is one of a set of two parallel cables.
Note:
(**) Indicates that a 1.5" conduit orifice is required if using the recommended cable
size.
G7 ASD Quick Start Guide
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 8. 600-volt G7 ASD Cable/Terminal Specifications.
Typical Wire/Cable Size (AWG or kcmil)
Input/Output Power
AM, FM, and II
Terminals
Maximum
14
10
14
10
14
10
14
10
14
10
14
10
10
10
10
4
8
4
8
4
(3-core shield)
6
4
6
4
4
2
3
2
1
*4/0
2/0
*4/0
3/0
*4/0
*2/0
*500
*3/0
*500
*4/0
*500
Control Terminals
20
18
(2-core shield)
Lug Size Range
Wire-Size/Lug-Capacity for
Input/Output Power
24 to 8
18 to 4
16 to 1
*(6 to 250)
*(1/0 to 500)
53