Postcomp Frequency — Displays the Output Frequency after the application of the slip
compensation correction value.
Feedback (inst.) — Provides a status of the Real Time Feedback in Hz.
Feedback (1 second) — Provides a status of the 1-Second Averaging feedback in Hz.
Torque — Displays the Output Torque as a percentage of the rated capacity of the G7.
Torque Reference — Displays the Torque Reference as a percentage.
Torque Current — Displays the current being used to produce torque.
Excitation Current — Displays the current required to produce the excitation field.
PID Value — Displays the PID feedback value in Hz (Proportional-Integral-Derivative).
Motor Overload — Displays the Motor Overload value as a percentage of the rated capacity of the
motor.
ASD Overload — Displays the ASD Overload as a percentage of the rated capacity of the G7.
DBR Overload — Displays the DBR Overload value as a percentage of the Dynamic Braking
Resistor capacity.
Motor Load — Displays the Motor Load in real time as a percentage of the rated capacity of the
motor.
ASD Load — Displays the ASD Load as a percentage of the rated capacity of the G7.
DBR Load — Displays the DBR Load as a percentage of the Dynamic Braking Resistor capacity.
Input Power — Displays the Input Power in Kilowatts (Kw).
Output Power — Displays the Output Power in Kilowatts (Kw).
Peak Current — Displays the Peak Current since the last start was initiated. The current is
displayed as a percentage of the rated capacity of the G7.
Peak Voltage — Displays the Peak Voltage since the last start was initiated. The voltage is displayed
as a percentage of the rated capacity of the G7.
PG Speed — Displays the PG Speed.
Direction — Displays the Direction command (forward/reverse).
PG Position — Displays the Pulse Generator Position.
RR — Displays the RR input value as a percentage of the full range of the RR value (potentiometer
input).
*VI/II — Displays the VI/II input setting as a percentage of the full range of the VI/II value.
Note:
* The VI/II input represents two analog inputs (and terminals). The VI input
terminal is used for a 0 – 10 VDC analog signal and the II input terminal is used
for current loop applications, such as with a 4-20 mA signal. Either may be used
as a frequency or torque command source; however, the two cannot function
simultaneously. Throughout this manual they will be listed as VI/II.
RX — Displays the RX input setting as a percentage of the full range of the RX value (-10 to
+10 VDC input).
RX2 — Displays the RX2 input setting as a percentage of the full range of the RX2 value.
Note:
The RX2 function is available on the ASD-Multicom option board only.
FM — Displays the output frequency value as a percentage of the full range of the FM value.
AM — Displays the output current as a percentage of the full range of the AM value.
Option Type — Displays the type form number of the installed ASD-Multicom option board.
Option Term A — TBD.
Option Term B — TBD.
Option Term O — TBD.
Option Term P — TBD.
Max. Output — TBD.
Pattern Select — Active Group Number and Speed Number separated by a period (e.g., 2.3).
Repeats Left — Number of remaining Speed cycles in the active Group.
Pattern — Active Speed Number of the Group.
Pattern Time Left — Time remaining in the active Speed.
Fault Status — Displays the current fault or No Fault.
G7 ASD Quick Start Guide