Contents displayed by DSP2
H0
COMM. Fault between IR341 and main chip.
H1
COMM. Fault between communication chip and main chip.
H4
3 times of P6 protection in 30 minutes.
H5
3 times of P2 protection in 30 minutes.
H7
The number of indoor units decreases.
H8
Reserved.
HF
M-HOME for the indoor and outdoor units does not match.
E1
Reserved.
E2
Communication fault between the outdoor and indoor units.
E4
T3 & T4 temperature sensor fault.
E5
Voltage protection fault or a leak of Phase B, Phase N.
E6
DC fan motor fault.
E7
Discharge temperature sensor fault.
EA
A fan in the A region run for more than 5 minutes in Heating mode.
Eb
2 times of E6 protection in 10 minutes.
P0
Inverter compressor top high temperature protection.
P1
High pressure protection.
P2
Low pressure protection.
P3
Outdoor input current protection.
P4
Compressor discharge high temperature protection.
P5
Outdoor condenser high temperature protection.
P6
Inverter module protection.
P8
Typhoon protection.
PE
Evaporator high temperature protection.

5. Electric Characteristics

Model
ASDH-96AI
Note:
MCA: Min. Current Amps. (A)
MFA: Max. Fuse Amps. (A)
RLA: Rated Locked Amps. (A)
FLA: Full Load Amps. (A)
Outdoor Unit
Hz
Voltage
Min.
50
380-415V
342V
Power Supply
Max.
MCA
TOCA
440V
/
23
TOCA: Total Over-current Amps. (A)
MSC: Max. Starting Amps. (A)
OFM: Outdoor Fan Motor
KW: Rated Motor Output (kW)
11
Compressor
MFA
MSC
RLA
40
/
15.4
OFM
KW
FLA
0.17
1.7