NT20S Status Control
Reference: Instead of turning Bit 15 ON, a screen can be displayed by specifying its screen
192
S Screen display (bit 15)
The screen display bit is used to display and clear the screen to prevent "burn-in"
on the CRT. Set bit 15 to 0 (OFF) to clear the screen. The backlight will also go
OFF at the same time.
When the screen has been cleared, the last displayed screen can be redisplayed
either by turning Bit 15 ON, or by pressing a touch switch. The backlight will also
light at the same time.
Note that if the screen is OFF by the backlight OFF or EL screen OFF function
with Bit 15 ON (1), turn Bit 15 OFF (0) once and then turn it back ON (1) to redis-
play the screen.
number. For details on screen switching, see "Switching the Screen Display"
(page 157).
S Priority registration for processing (NT link 1:N connections only) (bit 14)
It is possible to register one of the multiple PTs connected by the 1:N NT link
method to have processing priority. The PT for which bit 14 is set ON (1) is given
priority over the other PTs and has a higher response speed for display, touch
switches, etc.
When bit 14 is turned OFF (0), this registration is canceled and the normal re-
sponse speed is reinstated. If priority registration is set for more than one PT, the
one for which the registration was made last will have priority.
By monitoring C200HX/HG/HE words, the unit number of the PT for which prior-
ity registration has been set can be confirmed. For details on the monitoring op-
eration at the PC side, refer to the manual for the PC used.
[Connection to RS-232C port of C200HX/HG/HE]
Channel
CI0265CH (standard port)
(
p
)

CI0284CH (port A) (
CI0284CH (
t A) ( )
)


CI0285CH (port B) (
CI0285CH (port B) (
)
)

(
) This is the port of the communication port.
Bit
0
Unit No.0 Communication in progress flag, ON when connected
1
Unit No.1 Communication in progress flag, ON when connected
2
Unit No.2 Communication in progress flag, ON when connected
3
Unit No.3 Communication in progress flag, ON when connected
4
Unit No.4 Communication in progress flag, ON when connected
5
Unit No.5 Communication in progress flag, ON when connected
6
Unit No.6 Communication in progress flag, ON when connected
7
Unit No.7 Communication in progress flag, ON when connected
8
Unit No.0 Priority registration lamp, ON when registered
9
Unit No.1 Priority registration lamp, ON when registered
10
Unit No.2 Priority registration lamp, ON when registered
11
Unit No.3 Priority registration lamp, ON when registered
12
Unit No.4 Priority registration lamp, ON when registered
13
Unit No.5 Priority registration lamp, ON when registered
14
Unit No.6 Priority registration lamp, ON when registered
15
Unit No.7 Priority registration lamp, ON when registered
Section 5-4