Emerson E2 Installation And Operation Manual page 18

Eaton breaker panel
Hide thumbs Also See for E2:
Table of Contents

Advertisement

troller:Application:Property from the
Board:Point format.
5.
For the Controller property, press
LOOK UP to select the Eaton Breaker Panel,
for the Application property select Lighting
Panel, and for the Inputs property select the
breaker numbers that are included in the
group.
Figure 4-9 - Grouping Inputs in Digital Combiner
6.
Go back to the Lighting application under the
More tab and associate the Lighting group
(Figure 4-10) with the Digital Combiner ap-
plication:
Figure 4-10 - The Digital Combiner Used To Group Inputs
When using the Digital Combiner method above,
the Proof Type must be set to ON Only.
7.
Under the More tab, change the PROOF IN
12 • Eaton Panel Breaker
 -
8.
For more information on setting up Lighting
Schedules, refer to the Lighting Schedules section in
the E2 User Manual (P/N 026-1610).
format by pressing
Alternate I/O Formats to Area Ctrl:Appli-
cation:Property from the Board:Point for-
mat.
For the Area Ctrl property, press
LOOK UP to select the E2 Name, for the Ap-
plication property select the Digital Combin-
er that you created, and for the Output
property select OUTPUT.
026-1709 Rev 2 28-JUN-2011