Add And Connect Eaton Breaker Panels - Emerson E2 Installation And Operation Manual

Eaton breaker panel
Hide thumbs Also See for E2:
Table of Contents

Advertisement

7.
Press
+
General Controller Info setup screens:
Figure 3-8 - Serial Communications Manager Screen
8.
This screen will have a "Connection" field
for all COM ports on the E2. Highlight the
COM port connection field that will be used,
and press
of network types, select MODBUS-1, MOD-
BUS-2, or MODBUS-3.
9.
Four fields will become visible underneath
the COM port connection field, which pertain
to the way the device communicates:
•Baud - Change Default setting to 9600.
•Data Size - Leave this field at the default
value (8).
•Parity - Leave this field at the default value
(None).
•Stop Bits - Leave this field at the default
value (1).
10. Press
E2 Setup of Eaton Breaker Panels
to open the Serial tab of the
- LOOK UP. From the list
to save changes and exit.
3.4.3. Add and Connect Eaton Breaker
Panels
To enable communications between E2 and the
Eaton Breaker Panels, the devices must be added and
addressed in E2.
1.
Log in to the E2 with Level 4 access.

2.
Press
Boards and Controllers.
Figure 3-9 - Connected I/O Screen
3.
On the Connected I/O screen, in a box labeled
Third Party Devices, enter the number of
Eaton Breaker Panels in the Eaton Breaker
Panel number field.
4.
Press
menu, then select
(Figure 3-10).
5.
Locate the Eaton Breaker Panels you added
to the network list (press
through the list) and highlight with the cursor.
The default name for a Eaton Breaker Panels
begins with a three-letter designator of the
model type (ETN for Eaton). Press
Setup.
- Connected I/O
to return to the Network Setup
- Network Summary
and
to scroll
Networking • 7