Figure 3-10 - Network Summary Screen
6.
To set the address and begin communication,
press  and select  - "Select Address."
In the list of MODBUS devices, choose the
address number corresponding to the Eaton
Breaker Panel's address switch (Figure 3-2)
setting, and press  to select it. For a two
rail system, the user will select the left rail ad-
dress and the right rail address will automati-
cally be addressed as the left rail address + 1
7.
Locate the Eaton Breaker Panels you set up,
and look at each device's status in the Status
field. You will see one of the following mes-
sages:
•Online - The Eaton Breaker Panel is com-
municating normally.
•Offline - The Eaton Breaker Panel is not
communicating, has not been commis-
sioned, is not functional, or is not powered
up. Verify the Eaton Breaker Panel is pow-
ered up, wired correctly, and has the proper
network address, baud rate, and parity (see
Section 5, ).
•No Port - No port is set up in the E2 Serial
Configuration Manager to be a MODBUS
port. Follow the instructions in Section
3.4.2.
8 • Eaton Panel Breaker
026-1709 Rev 2 28-JUN-2011