MMD-TA-11B / MMD-TA-12B Muting Module
Instruction Manual
Appendix A. Mute Timing Sequences
Muting Sequence with Two Muting Devices
(For example, "X"-pattern Entry/Exit System,
see Figure B-1)
DIP Switch Configuration*:
MSSI Auto or Manual Reset. . . .SW1 = OFF (Manual)
SSI Auto or Manual Reset . . . . .SW2 = OFF (Manual)
One-Way Muting . . . . . . . . . . . .SW3 = OFF (1-way)
Two-/One-Channel EDM . . . . . .SW4 = OFF (2 CH)
Backdoor Timer . . . . . . . . . . . . .SW5&6 = OFF (30 sec.)
Monitored Muting Lamp . . . . . . .SW7 = OFF (Mon)
Mute on Power-up . . . . . . . . . . .SW8 = OFF (Disable)
*Both DIP switch banks A and B.
Muting Sequence with Four Muting Devices
(For example, an Entry/Exit System using four
photoelectric devices; see Figure B-5)
DIP Switch Configuration*:
MSSI Auto or Manual Reset. . . .SW1 = OFF (Manual)
SSI Auto or Manual Reset . . . . .SW2 = OFF (Manual)
One-Way Muting . . . . . . . . . . . .SW3 = OFF (1-way)
Two-/One-Channel EDM . . . . . .SW4 = OFF (2 CH)
Backdoor Timer . . . . . . . . . . . . .SW5&6 = OFF (30 sec.)
Monitored Muting Lamp . . . . . . .SW7 = OFF (Mon)
Mute on Power-up . . . . . . . . . . .SW8 = OFF (Disable)
*Both DIP switch banks A and B.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Power
ON
MSSI
System Reset
AUX Outputs
OFF
(open)
MMD-TA-11B
OFF
or ON (Auto)
(open)
OSSD Outputs
EDM
Closed
Mute Enable
Open
M1
{
Mute
Inputs
M2
Mute Cycle
Power
ON
MSSI
System Reset
OFF
AUX Outputs
(open)
MMD-TA-11B
OFF
or ON (Auto)
(open)
OSSD Outputs
EDM
Closed
Open
Mute Enable
M1
{
Mute
Inputs
M2
M3
{
Mute
Inputs
M4
Mute Cycle
NOTE: A mute cycle begins 100 ms after the second
mute input becomes active, if all other
conditions are met.
Open
Open
Closed
Reset
ON (closed)
ON (closed)
Open
Closed
Closed
Closed
Mute
Less than
3 seconds
Normal mute cycle
Mute cycle prevented
OSSD outputs
due to open
remain ON
Mute Enable input
Open
Closed
Reset
ON (closed)
ON (closed)
Open
Closed
Closed
Closed
Closed
Mute
Less than
3 seconds
One-Way Muting:
Normal mute cycle
Mute cycle prevented
OSSD outputs
due to mute devices
remain ON
M3 and M4 closing
before M1 and M2.
Two-Way Muting:
A normal mute cycle
would occur.
Appendix A
Open
Reset
Reset
OFF (open)
OFF (open)
OFF (open)
OFF (open)
Closed
More than
3 seconds
Mute cycle prevented
due to simultaneity
not being met
Open
Open
Reset
OFF (open)
OFF (open)
OFF (open)
OFF (open)
Mute
Mute cycle drops out
and the OSSD outputs open due
to M3 and M4 not closing before
M1 or M2 open, when the
defined area is blocked.
Since one-way muting has been
selected, M3 and M4 can not
initiate a mute cycle.