ICP DAS USA I-7530 User Manual page 20

I-7530 series uart to can bus converter
Hide thumbs Also See for I-7530:
Table of Contents

Advertisement

Status
JP4 position
Enable (default)
(Activate)
I-7565
Disable (Deactivate)
There is no terminator resistor in the tM-7530. Therefore, if users would like to use terminator
resistor, it is necessary to wire a 120Ω resistance on the CAN bus, as following figure.
The terminator resistor is built in the tM-7530A. If users would like to enable terminator resistor of
the tM-7530A, please let the CAN_H pin and the TR pins be shorted to each other, as following
figure.
20
I-7530, I-7530-FT, I-7530A, I-7565, tM-7530, tM-7530A User Manual
Version 1.4