Vent System - IDEAL Vogue System Gen 2 S15 Installation And Servicing

Table of Contents

Advertisement

MENU OPERATION - CONT'D
FAULT HISTORY
To view the Fault History of the boiler
press MENU and the following screen
will be displayed.
MENU
SHOW EFFICIENCY LEVEL
SERVICE COMPANY NAME
SERVICE COMPANY PHONE NUMBER
SELECT
EXIT
Press
until the following screen is
displayed.
MENU
CHANGE SERVICE INTERVAL
FAULT HISTORY
FAULT HELP

VENT SYSTEM

SELECT
EXIT
Press SELECT and a screen similar to
the following will be displayed.
FAULT HISTORY
MENU
LOW WATER PRESSURE
TOTAL OCCURENCES:
SHOW EFFICIENCY LEVEL
4
MOST RECENT:
6 DAYS AGO
HOT WATER PREHEAT ON / OFF
SERVICE COMPANY PHONE NUMBER
PREV
NEXT
EXIT
SERVICE COMPANY NAME
Press
and
to view the full list.
SELECT
Press EXIT twice to return to normal
operation.
40
SECTION 2 - INSTALLATION
FAULT HELP
This feature provides a list of potential
corrective actions at an installer level
for all faults detectable by the boiler
electronics Press MENU and the
following screen will be displayed
MENU
SHOW EFFICIENCY LEVEL
SERVICE COMPANY NAME
SERVICE COMPANY PHONE NUMBER
Press
until the following screen is
displayed.
MENU
FAULT HISTORY
FAULT HELP
VENT SYSTEM
SENSOR READINGS
Press SELECT and the following screen
will be displayed.
FAULT HELP
LOW WATER PRESSURE
OFF
MAX
IGNITION LOCKOUT
SHOW EFFICIENCY LEVEL
NO WATER FLOW
HOT WATER PREHEAT ON / OFF
SERVICE COMPANY PHONE NUMBER
EXIT
SERVICE COMPANY NAME
Press
and
shown then press SELECT and a screen
OFF
MAX
similar to the following will be shown.
LOW WATER PRESSURE
With boiler o & system cold
fill system to between 1.0 & 1.5 bar
Bleed radiators then refill.
If fault persists contact Ideal (01482 498660)
If pressure loss re-occurs contact installer
Press EXIT swich when finished.
VENT SYSTEM
The Vent System feature aids removal of
air from the heat exchanger. The pump
will be switched on for 50s and then off
for 10s while the diverter valve is moved
between DHW and CH every 30s. The
feature lasts for 5 minutes.
Press MENU and the following screen
will be displayed.
SELECT
EXIT
Press
displayed.
SELECT
EXIT
Press SELECT and the following screen
MENU
will be displayed.
OFF
SELECT
EXIT
until the desired fault is
SELECT
EXIT
OFF
The feature will end automatically after 5
minutes, to end manually press END.
EXIT
MENU
SHOW EFFICIENCY LEVEL
SERVICE COMPANY NAME
SERVICE COMPANY PHONE NUMBER
SELECT
EXIT
and the following screen is
MENU
FAULT HELP
VENT SYSTEM
SENSOR READINGS
PUMP / FAN / VALVES
SELECT
EXIT
MAX
VENT SYSTEM
PUMP SPINS ON 50s, OFF 10s
DIVERTER VALVE ALTERNATES CH/DHW
05:00
MINUTES REMAINING
END
+30 secs
-30 secs