2.25 CHECK CH & HW CYLINDER OPERATION
OPERATION WITHOUT OUTSIDE SENSOR
When the burner is established the following screen will
be displayed.
ON
60
C
O
MENU
The temperature shown will be the actual Flow
Temperature.
At full output, check the gas rate at the gas meter with no
other appliances in use. Refer to Table 2 for gas rates.
Ensure that, with the boiler operating, the dynamic gas
pressure is able to obtain maximum output. Refer to
Table 1.
Set the timer to be off. The burner will go off and the fan
and pump continue to run for 2 minutes. The following
screen will be displayed.
READY
TIMER OFF OR ROOM THERMOSTAT
AND CYLINDER THERMOSTAT OFF
MENU
Check the correct operation of all the system controls
by operating each control separately and check that the
main burner responds.
IMPORTANT
The gas input to the burner is regulated by the gas valve according to the air flow produced by the fan. It is NOT user-
adjustable. Any interference to sealed settings on the gas valve will adversely affect operation and render warranty void. For
additional information refer to Section 1.8 Gas SupplY.
Installation and Servicing
SECTION 2 - INSTALLATION
OPERATION WITH OUTSIDE SENSOR
With all the system controls calling for heat, when the
burner is established the following screen will be displayed.
ON
ON
60°C
60°C
60
O
C TO CYLINDER
15°C
MENU
The temperature shown will be the actual Flow
temperature.
At full output check the gas rate at the gas meter with no
other appliances in use. Refer to Table 2 for gas rates.
Ensure that, with the boiler operating, the dynamic gas
pressure is able to obtain maximum output. Refer to Table 1.
Set the timer to be off. The burner will go off and the fan
and pump continue to run for 2 minutes. The following
screen will be displayed.
READY
READY
TIMER OR CYLINDER
TIMER OR ROOM
THERMOSTAT OFF
THERMOSTAT OFF
15°C
MENU
Check the correct operation of all the system controls by
operating each control separately and check that the main
burner responds.
37