DM Area Allocations

4-4

DM Area Allocations

Offset
Bit
15
m
Internode test remote network address and node number
m+1
Internode test number of send bytes
m+2
Internode test response monitoring time
m+3
Internode test status
m+4
Number of internode test runs
m+5
Number of internode test timeout errors
m+6
Number of internode test response errors
m+7
Number of internode test send errors
m+8
Number of times internode test data did not match
m+9
TCP socket No. 1 connection status
m+16
TCP socket No. 8 connection status
m+17
Mail status
Socket Services Parameter Area 1
m+18
Socket Services Parameter Area 2
m+28
m+88
Socket Services Parameter Area 8
m+98
IP Address Display Area
m+99
Internode Test Remote Network Address and Node Number (CPU Unit to Ethernet Unit)
Internode Test Number of Send Bytes (CPU Unit to Ethernet Unit)
56
The various kinds of data are stored in the offset positions shown in the following
diagram, from the beginning word in the area for each Unit.
The beginning word m is calculated by the following equation:
Beginning word m = D30000 + (100 x unit number)
8
7
0
The meanings of the items shown in the above diagram are explained on the
following pages. For details regarding the related communications services
shown in the diagram, refer to the indicated sections.
15 14 13 12 11 10
m
Remote network address
Specify the remote network address and node number in hexadecimal within the
following ranges:
Remote network address: 00 to 7F Hex (0 to 127 decimal)
Remote node number: 01 to 7E Hex (0 to 126 decimal)
If a remote network address is set to 00, it will specify the local network (i.e., the
network to which the Ethernet Unit is connected.)
15 14 13 12 11 10
m+1
Specify, in hexadecimal, the number of bytes of test data to be sent between
nodes.
0000 (Hex): 1,996 bytes
0001 to 07CC (Hex): 1 to 1,996 bytes
Related communications services
Data direction
CPU Unit to Ethernet Unit
Ethernet Unit to CPU Unit
CPU Unit to Ethernet Unit
Ethernet Unit to CPU Unit
9
8
7
6
Remote node number
9
8
7
6
Number of send bytes (0000 to 07CC Hex)
Section
Internode Test Function
(Refer to 9-3 Internode Test.)
Socket Services
(Refer to Section 6
Socket Services.)
Mail function
(Refer to Section 8 Mail.)
Socket Services
(Refer to Section 6
Socket Services.)
5
4
3
2
1
0
5
4
3
2
1
0
4-4