Omron CS1W-ETN01 Operation Manuals page 44

Sysmac cs1 series ethernet unit
Hide thumbs Also See for CS1W-ETN01:
Table of Contents

Advertisement

Connecting to the Network
General Switching Power Supply Configuration
AC power supply
Communications Power Supply Isolation Method
S82Y-jjN (Mounting Stand)
(1) When S82J is used.
Power Supply
Specifications
terminal it is necessary to insulate the power supply itself from the control
panel.
Switching power supply
Power
supply
AC input
circuit
Standard Switching Power Supply Circuit
S8J2 Power Supply
17. If communications are adversely affected by noise from the Unit's power
supply terminals, the problem may be solved by implementing the mea-
sures shown below.
a) Add to the communications retry processing at the application. In partic-
ular, noise resistance capacity can be improved by increasing the num-
ber of retries for applications using UDP.
b) Insert a noise filter right next to the Unit's power supply terminals.
24 VDC
As close as possible
Recommended filter: MAS-1206-33 by Nemic-Rambda K.K.
Specifications
Dimensions
The following table shows the power supply specifications. Make sure that these
specifications are met.
Item
Power supply voltage
Allowable power supply voltage
fluctuation
Current consumption
Inrush current
OMRON's S82J Series is recommended for the power supply.
DC output
Case
DC power supply
Insulating material (bakeboard, acrylic board, etc.)
(2) When another power supply is used.
Noise filter
Rated voltage: 250 V (AC, DC)
Rated current: 6 A
105.5 x 52.5 x 40 mm (W x H x D)
(Not including connector.)
24 VDC
20.4 VDC to 26.4 VDC (24 VDC –15% + 10 %)
300 mA max. at 24 VDC (per node)
2.5 A max. (24 VDC when rise time is 5 ms)
Section
24-VDC power supply
Specifications
3-6
31