Creating Routing Tables; Routing Table Overview - Omron CS1W-ETN01 Operation Manuals

Sysmac cs1 series ethernet unit
Hide thumbs Also See for CS1W-ETN01:
Table of Contents

Advertisement

Creating Routing Tables

3-8

Creating Routing Tables

3-8-1 Routing Table Overview

Use the following procedure to create the I/O table.
Initial screen
000000 I/O TBL ?
CHG
000000 I/O TBL
WRIT
????
000000CPU BU ST?
0:CLR 1:KEEP
000000 I/O TBL
WRIT OK
When the FINS communications service is used, routing tables must be created
in advance. Routing tables are required in the following circumstances.
• When the FINS communications service is used on an Ethernet network (in-
cluding when communications are only carried out between FA networks via
an Ethernet network).
• When there are multiple Communications Units mounted to the PC, and sock-
et services are requested by executing the CMND(490) instruction.
If neither of these circumstances apply, then a routing table is not required. In
that case, proceed to 3-9 System Setup.
The routing table is required not only for nodes communicating via the FINS
communications service but for all relay nodes on the network.
The routing tables describe the transmission path for FINS messages when the
FINS communications are used. It consists of two tables: A local network table
and a relay network table.
CH
SHIFT
:DM
WRITE
Password
(Save or clear the CPU Bus Unit System Setup.)
or
Section
3-8
33

Advertisement

Table of Contents
loading

Table of Contents