Omron CS1W-ETN01 Operation Manuals page 198

Sysmac cs1 series ethernet unit
Hide thumbs Also See for CS1W-ETN01:
Table of Contents

Advertisement

Results Storage Area Response Codes
Response
UNIX error
code
message
0053
ETIMEDOUT
0063
ESELABORT
0066
(None)
0080
(None)
0081
(None)
0082
(None)
188
Description
Connection timed out (TCP timed
out)
Used for internal Ethernet Unit pro-
cessing
Internal memory cannot be
allocated for processing; the
service cannot be provided.
Timed out for passive TCP open re-
quest
Closed by close command during
socket servicing
Connection with remote node not
achieved for passive TCP open re-
quest
Probable remedy
Check the remote host and communications
path.
Close the local socket and try reopening it.
Traffic is too high at the Ethernet Unit. Correct
the user application to reduce traffic at the
Ethernet Unit.
Either the remote node is not executing an ac-
tive TCP open or there is a block on the net-
work.
No action is necessarily called for.
The remote IP address and TCP port number
settings differ from those of the remote socket
(active side).
Section
10-7

Advertisement

Table of Contents
loading

Table of Contents