CPU Bus Unit System Setup

CIO Area Allocations
DM Area Allocations
4-2

CPU Bus Unit System Setup

Unit No.
(decimal)
0 (0)
CIO 1500 to CIO 1524
1 (1)
CIO 1525 to CIO 1549
2 (2)
CIO 1550 to CIO 1574
3 (3)
CIO 1575 to CIO 1599
4 (4)
CIO 1600 to CIO 1624
5 (5)
CIO 1625 to CIO 1649
6 (6)
CIO 1650 to CIO 1674
7 (7)
CIO 1675 to CIO 1699
Unit No.
(decimal)
0 (0)
D30000 to D30099
1 (1)
D30100 to D30199
2 (2)
D30200 to D30299
3 (3)
D30300 to D30399
4 (4)
D30400 to D30499
5 (5)
D30500 to D30599
6 (6)
D30600 to D30699
7 (7)
D30700 to D30799
To operate the Ethernet Unit as a node on an Ethernet network, the required pa-
rameters must be set in the CPU Bus Unit System Setup, part of the CPU Unit's
Parameter Areas. If any of the following items apply, then the system parame-
ters must be set.
• Either the IP address table or both the IP address table and automatic address
generation are used as the destination IP address conversion method.
• Transmissions are broadcast using a host number set to all zeroes as the
broadcast address (when UNIX 4.2BSD specifications are used for the broad-
cast address).
• The FINS UDP port number is set to a value other than 9600.
• A subnet mask other than the one determined from the IP address is set.
• A login name other than CONFIDENTIAL is used for the FTP server function.
• Communications between segments are required.
• The mail function is used.
Newly set parameters go into effect after the Ethernet Unit has been restarted or
after the CPU Unit is started again.
The settings are made using the CX-Programmer.
Note The CPU Bus Unit System Setup is located in the CPU Unit's Parameter Area,
and not in I/O Memory; parameters cannot be written using instructions or by
editing I/O Memory. The settings can be made only using the CX-Programmer.
Allocated words
Unit No.
(decimal)
8 (8)
9 (9)
A (10)
B (11)
C (12)
D (13)
E (14)
F (15)
Allocated words
Unit No.
(decimal)
8 (8)
9 (9)
A (10)
B (11)
C (12)
D (13)
E (14)
F (15)
Section
4-2
Allocated words
CIO 1700 to CIO 1724
CIO 1725 to CIO 1749
CIO 1750 to CIO 1774
CIO 1775 to CIO 1799
CIO 1800 to CIO 1824
CIO 1825 to CIO 1849
CIO 1850 to CIO 1874
CIO 1875 to CIO 1899
Allocated words
D30800 to D30899
D30900 to D30999
D31000 to D31099
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599
43