Technical specifications
Digital outputs
Number of outputs
Short-circuit protection
Wire break detection
Voltage induced on current interruption limited to
Control of a digital input
Switching capacity of outputs
With resistive load, max.
With lamp load, max.
Load resistance range
Low limit
High limit
Output voltage
For "1" signal, min.
Output current
For "1" signal, rated value
For "0" signal, residual current, max.
Switching frequency
With resistive load, max.
With inductive load, max.
For capacitive load, max.
With lamp load, max.
Total current of outputs
Max. current per channel
Current per module, max.
Total current of the outputs (per module)
Horizontal mounting position
Vertical mounting position
Length of cable
shielded, max.
unshielded, max.
Interrupts/diagnostics/status information
Diagnostics function
Fail-safe values can be switched to
Interrupts
Diagnostic interrupt
48
Response threshold, typ.
Up to 40 ℃, max.
Up to 50 ℃, max.
Up to 60 ℃, max.
Up to 50 ℃, max.
8
Yes
min. 0.7 A
No
Typ. -39 V
Yes
0.5 A
2 W
48 Ω
12000 Ω
24 V; L+ (-0.5 V)
0.5 A
0.5 mA
30 Hz; symmetrical
0.1 Hz; according to IEC 60947-5-1, DC-13, bal-
anced
2 Hz; balanced
10 Hz; symmetrical
0.5 A; note derating information in the manual
3 A; note derating information in the manual
3 A
2.5 A
2 A
2 A
100 m
100 m
Yes, see section "Interrupts/diagnostics alarms"
in the manual
No
Yes
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
6ES7136-6DC00-0CA0
Manual, 05/2017, A5E38578424-AA