Parameters/address space

4.2 Explanation of parameters

4.2
Explanation of parameters
4.2.1

F-parameters

4.2.1.1
F-parameters
You must assign the PROFIsafe address (F-destination address together with F-source
address) to the F-module before you put it into operation.
● You define the F-source address using the "Base for PROFIsafe addresses" parameter in
the F-CPU.
● An F-destination address unique throughout the CPU is automatically assigned for each
F-module. You can manually change the F-destination addresses assigned in the
hardware configuration.
You can find information on F-parameters for the F-monitoring time, the PROFIsafe address
assignment (F-source address, F-destination address) and the F I/O DB in the manual
SIMATIC Safety - Configuring and Programming
(http://support.automation.siemens.com/WW/view/en/54110126).
4.2.1.2

Behavior after channel fault

This parameter is used to specify whether the entire F-module is passivated or just the faulty
channel(s) in the event of channel faults:
● "Passivate the entire module"
● "Passivate channel"
4.2.1.3

Reintegration after channel fault

Use this parameter to select how the channels of the fail-safe module are reintegrated after a
fault.
Use in S7-300/400 F-CPUs
This parameter is always set to "Adjustable" when you use the fail-safe module in S7-
300/400 F-CPUs.
You make the required setting in the F-I/O DB of the fail-safe module.