Siemens SIMATIC ET 200SP Manual page 45

Digital output module f-dq 8x24vdc/0.5a pp hf (6es7136-6dc00-0ca0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Diagnostics alarm
Short-circuit to ground
Invalid/inconsistent firmware
present
Channel failure acknowl-
edgment
F-address memory not ac-
cessible
Frequency too high
Undertemperature
Supply voltage too high
Supply voltage too low
Supply voltage outside the nominal range
If the supply voltage L+ is outside the specified value range, the DIAG LED flashes and the
module is passivated.
When the voltage is then recovered (level must remain within the specified value for at least
1 minute (see Technical specifications (Page 47) Voltages, Currents, Potentials)), the DIAG
LED stops flashing. The module remains passivated.
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
Manual, 05/2017, A5E38578424-AA
Fault
Meaning
code
262
Short-circuit to ground can mean:
D
The output cable is short-circuited to
ground.
The output signal is short-circuited to
ground.
The capacitive load is too high.
You must eliminate the error within 100
hours; otherwise, the F-module is perma-
nently passivated and an acknowledg-
ment is no longer possible.
283
The firmware is incomplete and/or firm-
D
ware added to the F-module is incompat-
ible. This leads to errors or functional
limitations when operating the F-module.
779
A channel fault was detected. Confirma-
D
tion is required to enable the channel.
781
The F-source address and F-destination
D
address stored in the coding element
cannot be accessed.
785
The maximum switching frequency of the
D
F-module has been exceeded.
786
The minimum permissible temperature
D
limit has been violated.
801
The supply voltage is too high.
D
802
The supply voltage is too low.
D
Interrupts/diagnostic messages
6.3 Diagnostics alarms
Solution
Correct the process wiring.
Increase the test times (dark, light).
Check the actuator.
Perform a firmware update for all
parts of the F-module and note any
error messages.
Use only firmware versions re-
leased for this F-module.
Confirm the channel fault.
Verify that the coding element is pre-
sent or replace the coding element.
Reduce the switching frequency (see
Technical specifications (Page 47))
Operate the F-module within the speci-
fied temperature range (see Technical
specifications (Page 47))
Once the temperature has increased
and returns to the specified range, the
F-module must be removed and in-
serted or the power switched OFF and
ON.
Check the supply voltage.
Check the supply voltage.
45