Adding Setting Groups - ABB 650 series Engineering Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

Section 9
DNP3 communication engineering
9.2
104

Adding setting groups

In order to show for a DNP master which setting group is used, the following
procedure can be performed.
In this example, only setting groups one and two are used. The DNP master will
get two binary inputs: the first is set if setting group one is used, the second is set if
setting group two is used.
1.
Configure ACTVGRP (Basic IED functions) and SP16GGIO (Monitoring)
with the Application Configuration Tool (ACT).
IEC11000423 V1 EN
Figure 72:
Application configuration tool
To make it easier to recognize the signals for the active setting
group, the user-defined names are used.
2.
Open the Communication Management Tool (CMT). Set the Signal Type to
Binary Input Object and choose the connection of the master for which the
values should be presented.
1MRK 511 261-UEN -
IEC11000423-1-en.vsd
650 series
Engineering Manual

Advertisement

Table of Contents
loading

Table of Contents