1MRK 511 261-UEN -
650 series
Engineering Manual
The physical connection and the IP address must be configured in both cases to
enable communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match
the IP addresses of the physical IEDs.
Setting up IP addresses
The IP address and the corresponding mask must be set via the LHMI for each
available Ethernet interface in the IED. Each Ethernet interface has a default
factory IP address when the IED is delivered. This is not given when an additional
Ethernet interface is installed or an interface is replaced.
The default IP address for the IED front port is 10.1.150.3 and the
corresponding subnetwork mask is 255.255.255.0, which can be set via the
local HMI path Main menu/Configuration/Communication/TCP-IP
configuration/1:ETHFRNT.
The default IP address for the IED rear port is 192.168.1.10 and the
corresponding subnetwork mask is 255.255.255.0, which can be set via the
local HMI path Main menu/Configuration/Communication/TCP-IP
configuration/1:ETHLAN1 and Rear OEM - port CD.
The front and rear port IP addresses cannot belong to the same
subnet or communication will fail. It is recommended to change the
IP address of the front port, if the front and rear port are set to the
same subnet.
Setting up the PC or workstation for point-to-point access to IEDs
front port
A special cable is needed to connect two physical Ethernet interfaces together
without a hub, router, bridge or switch in between. The Tx and Rx signal wires
must be crossed in the cable to connect Tx with Rx on the other side and vice
versa. These cables are known as cross over cables. The maximum length should
be about 2 m. The connector type is RJ-45.
Section 4
Setting up a project
27