1MRS757278
3.4.4.
COM600 series, Version 4.1
FDIR Configuration Manual
Figure 3.4.3-1 FDIR Configuration Tool - Network Setup
On the Switch tab, you can enable or disable the switch to be included in the FDIR net-
work. You can also change the capacity limit on the switch. FDIR also supports single
phase switch in the network. When single phase is selected, you can select the switch
for phase B and phase C. Phase B and Phase C switch should be disabled from the FDIR
network.
On the Source tab, you can enable or disable the source to be included in the FDIR net-
work. Also you can change the capacity limit on the source.
On the Load tab, you can enable or disable the load to be included in the FDIR network.

Setting parameters for setting groups

In the Group Settings tab, you can set parameters for setting groups, the range to
activate the setting group, a data object to read the current setting group number, and a
data object to send a command to change the setting group.
FDIR_network_setup
17