Section 8 Iec 60870-5-103 Communication Engineering; Engineering In Pcm600; Selecting To Communicate Iec60870-5-103 Data Via Rs485 Serial Interface On Com05 Module - ABB 650 series Engineering Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 261-UEN -
Section 8
8.1
8.1.1.1
650 series
Engineering Manual
IEC 60870-5-103 communication engineering
IEC 60870-5-103 communication
engineering

Engineering in PCM600

The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in
PCM600 are used to configure the communication for IEC 60870-5-103 protocol.
1.
Add the desired IEC 60870-5-103 function blocks to the application
configuration in the Application Configuration tool.
2.
Connect the outputs of desired protection and monitoring function in the
application configuration to the inputs of the corresponding IEC 60870-5-103
function block.
3.
Set the function type and desired information number, where an information
number must be supplied, for each IEC 60870-5-103 function block instance
in the Parameter Setting tool.
4.
Set the general communication settings for IEC 60870-5-103, available in
function RS485103 or OPTICAL103 depending on choice of serial interface,
and time synchronization parameters in the Parameter Setting tool.
See the Communication protocol manual for IEC 60870-5-103 for more
information about the IEC 60870-5-103 implementation in 650 series.
The COM05 module is equipped with an optical serial and RS485
serial communication interface. IEC60870-5-103 can be
communicated from either of these serial interfaces. The user must
select in PST which interface to use.
Selecting to communicate IEC60870-5-103 data via RS485 serial
interface on COM05 module
1.
In PST, navigate to the RS485PROT function block located in MainMenu/
IEDConfiguration/Monitoring/RS485PROT:1.
2.
To enable the IEC60870-5-103 protocol on the RS485 port, select IEC103 for
setting Operation.
3.
Navigate to the RS485103 function block, found in MainMenu/
IEDConfiguration/Communication/I103/RS485103:1, to set
IEC60870-5-103 communications port properties, such as baud-rate or master
time domain.