Specifications

8 Specifications

8.1 Electrical Data

8.1.1 Mains Supply 3x200-240 V AC

Type Designation
Typical Shaft Output [HP] at 208 V
6)
IP20/Chassis
Continuous (3x200-240 V) [A]
Intermittent (3x200-240 V) [A]
Continuous kVA (208 V AC) [kVA]
Continuous (3x200-240 V) [A]
Intermittent (3x200-240 V) [A]
Additional specifications
Estimated power loss at rated max. load [W]
IP20, IP21 max. cable cross-section (mains, motor, brake and load
sharing) [mm
2
/(AWG)]
IP55, IP66 max. cable cross-section (mains, motor, brake and load
2
3)
Table 8.1 Mains Supply 3x200-240 V AC - Normal overload 110% for 1 minute, P1K1-P3K7
MG11AK02
Operating Instructions
P1K1
1.1
1.5
A2
A4/A5
6.6
7.3
2.38
5.9
6.5
4)
63
0.96
Danfoss A/S © Rev. 06/2014 All rights reserved.
P1K5
P2K2
P3K0
1.5
2.2
3.0
2.0
2.9
4.0
A2
A2
A3
A4/A5
A4/A5
A4/A5
A5
7.5
10.6
12.5
8.3
11.7
13.8
2.70
3.82
4.50
6.8
9.5
11.3
7.5
10.5
12.4
82
116
155
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
4, 4, 4 (12, 12, 12)
6, 4, 4 (10, 12, 12)
0.96
0.96
0.96
P3K7
3.7
4.9
A3
A5
16.7
18.4
6.00
15.0
8
8
16.5
185
0.96
43