STO and SS1 safety functions
Example 3: OPTBJ board with SS1 and safety reset or EN 60204-1 stop category 1.
MAIN CIRCUIT
L1
L2
L3
PE
PE
1
3
5
F1
SPEED REFERENCE
2
4
6
R1
W12
1sh
1r
L1
L2
L3
1
+10Vref
2
7
U
V
W
PE
PE
PE
PE
W1
PE
U1
V1
W1
M
3
~
PE
Short circuit and earth
1
2
M1
fault protected supply
The figure above presents a connection example of OPTBJ board for SS1 safety function with ex-
ternal safety relay module and with safety reset.
The external safety relay module is connected to the switch S1. The used power supply to switch S1
is 230 VAC as an example. The safety relay module is connected to OPTBJ board with 4 wires as
shown in Figure above.
When the switch S1 is activated (contacts open), the drive will go to STO state and motor (if running)
will stop by coasting. The drive will indicate: "30 SafeTorqueOff".
To start the motor operation again, following sequence is performed.
Release the switch S1 (contacts closed). The hardware is now enabled but the drive continues to dis-
play the fault "30 SafeTorqueOff".
Acknowledge the releasing of switch by edge sensitive reset function. The drive returns to the ready
state.
Giving a valid start command will start running the motor
More information on the safety relay module may be found in the safety relay documentation.
NOTE! The Vacon 100 default application software uses edge-sensitive start as default start com-
mand, for preventing unexpected startup from STO state.
NOTE! For EN 60204-1 emergency stop according to stop category1, use emergency stop button.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
START
S6
CCW
13
S
14
CW
2sh 2p
2s
1
2
3
4
5
6
7
8
2
3
4
5
6
7
8
AI1+
AI1
AI2+
AI2
24Vout
GND
DI1
STO1+
STO1
STO2+
STO2
RO1 C
RO1 NO
TI1+
Installed
X10
X23
1
2
3
4
25
26
PE
PE
S1
24VDC
PE
W3
1r
2r
+
A10
57
67
13
23
33
41
A1
S10
PHOENIX CONTACT
A2
14
24
34
42
PSRSCP24DC/ESD/5X1/1X2/300
58
68
0VDC
0V
+24V
STOP
RAMP STOP
RS1
S7
11
12
9
10
11
12
13
14
15
9
10
11
12
13
14
15
16
DI2
DI3
CM
24Vout
GND
DI4
DI5
DI6
ON
OFF
RS485
U
I
AO1
U
I
AI2
U
I
AI1
ON
OFF DGND
TI1
OFF
OPTBJ
28
29
SLOT E
21
11
RESET
Bridge between S33/S35 for automatic reset.
(Not allowed with emergency stop)
12
22
S11 S12 S21
S22
S33
S34 S35
vacon • 25
16
17
18
19
20
21
22
17
18
19
30
A
B
CM
AO1+
AO/GND
+24Vin
RS485
RS485
Basic I/O
PE
3046A_UK
5