Vacon 100 Safety Manual page 26

Optbj sto and atex option board
Hide thumbs Also See for 100:
Table of Contents

Advertisement

vacon • 24
Example 2: OPTBJ board with reset for Safe Torque Off or EN 60204-1 stop category 0.
MAIN CIRCUIT
L1
L2
L3
PE
PE
1
3
5
F1
2
4
6
L1
L2
L3
U
V
W
PE
PE
PE
PE
W1
U1
V1
W1
M
~
3
PE
1
2
M1
The figure above presents a connection example of OPTBJ board for STO safety function with reset.
The switch S1 is connected with 4 wires to the OPTBJ board as shown above. The digital input 3
(DIN3), for example, is wired for the fault reset function. The reset function (not part of any safety
function) can be programmed to any of the available digital inputs.
The power supply to S1 may come from control board (connector pins 6 & 7 in Figure above) or it
may also be external, if earth fault and short circuit protected.
When the switch S1 is activated (contacts open), the drive will go to STO state and motor (if running)
will stop by coasting. The drive will indicate: "30 SafeTorqueOff".
To start the motor operation again, the following sequence is performed.
Release the switch S1 (contacts closed). The hardware is now enabled but the drive continues to dis-
play the fault "30 SafeTorqueOff".
Acknowledge the releasing of switch by edge sensitive reset function. The drive returns to the ready
state.
Giving a valid start command will start running the motor.
NOTE! The Vacon 100 default application software uses edge-sensitive start as default start com-
mand, for preventing unexpected startup from STO state.
NOTE! For EN 60204-1 emergency stop according to stop category 0, use the emergency stop but-
ton.
5
SPEED REFERENCE
CCW
R1
S
CW
W12
1sh
1r
2sh 2p
2s
1
2
3
4
5
6
1
2
3
4
5
6
+10Vref
AI1+
AI1
AI2+
AI2
24Vout
2
STO1+
STO1
STO2+
STO2
RO1 C
7
Installed
X10
1
2
3
4
W10
1r
1b
2r
2b
Safe torque off
11
21
S1
12
22
START
STOP
RESET
S7
S8
S6
13
13
11
14
14
12
7
8
9
10
11
12
13
7
8
9
10
11
12
13
GND
DI1
DI2
DI3
CM
24Vout
GND
ON
OFF
RS485
U
I
AO1
U
I
AI2
U
I
AI1
ON
OFF DGND
RO1 NO
TI1+
TI1
OFF
X23
OPTBJ
25
26
28
29
SLOT E
0V
Short circuit and earth
fault protected supply
+24V
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
STO and SS1 safety functions
14
15
16
17
18
19
20
21
14
15
16
17
18
19
30
A
DI4
DI5
DI6
CM
AO1+
AO/GND
+24Vin
RS485
3045A_UK
22
B
RS485
Basic I/O
PE