Siemens Simatic RF300 System Manual page 116

Hide thumbs Also See for Simatic RF300:
Table of Contents

Advertisement

Planning the RF300 system
4.5 Guidelines for electromagnetic compatibility (EMC)
4.5.5
Cabinet configuration
The influence of the user in the configuration of an electromagnetically compatible plant
encompasses cabinet configuration, cable installation, ground connections and correct
shielding of cables.
Note
For information about electromagnetically compatible cabinet configuration, please consult
the installation guidelines for SIMATIC PLCs.
Shielding by enclosure
Magnetic and electrical fields and electromagnetic waves can be kept away from the
interference sink by using a metal enclosure. The easier the induced interference current can
flow, the greater the intrinsic weakening of the interference field. All enclosures and metal
panels in the cabinet should therefore be connected in a manner allowing good
conductance.
Figure 4-13
If the control cabinet panels are insulated from each other, a high-frequency-conducting
connection can be established using ribbon cables and high-frequency terminals or HF
conducting paste. The larger the area of the connection, the greater the high-frequency
conductivity. This is not possible using single-wire connections.
116
Shielding by enclosure
System Manual, 07/2017, C79000-G8976-C345-07
SIMATIC RF300

Advertisement

Table of Contents
loading

Table of Contents