Review your plan to make sure all devices will fit in the cabinet. It is
also important to verify cabling lengths before installing any
enclosure.
Power distribution must support the number of outlets required for
the device and the device power rating.
Use the published technical specifications and device rating labels to
determine the current draw of each device in your cabinet and
calculate the total. Use the following values to calculate current draw
for CX3-series storage-system components.
These are maximum ratings for a class family, to guide the
Note:
sizing of power distribution components at the rack level. Since
configurations and drive types vary, they
estimate typical power consumption.
CX3-10//20
SPE3
1000 W SPS
(CX3-10)
0.2 A@ 100 V AC
2.4 A @ 100 V AC
0.1 A @ 200 V AC
1.5 A @ 200 V AC
Note: For high availability, the left and right sides of any rack or cabinet must
receive power from separate branch feed circuits.
may not be
appropriate to
SPE3
DAE3P
(CX3-20)
disk enclosure
3.3 A @ 100 V AC
4.4 A @ 100 V AC
1.9 A @ 200 V AC
2.2 A @ 200 V AC