List of error codes
o_wDiagCode
State name
(Hexadecimal)
C001H
Reset Error 1
C002H
Reset Error 2
C010H
Control Error
C111H
Init Error
C211H
Lock Error
List of status codes (no error)
o_wDiagCode
State name
(Hexadecimal)
0000H
Idle
8001H
Init
8002H
Safe
8003H
Lock
8010H
Output Disable
8000H
Output Enable
WARNING
Please do the above actions when the FB detects an error or is in an unexpected state. However, when the situation is still not corrected, please check the
following.
• A failure in safety devices and emergency stop devices
• Wiring and status of a safety remote I/O module and a safety programmable controller
• Programming logic, the memory allocation of safety devices, and the connections of safety FB variables
• Setting of i_bS_StartReset and i_bS_AutoReset
Description, output setting
Static i_bReset signal in state 8001H.
Static i_bReset signal in state 8003H.
Static signal at i_bProcessControl in state 8010H.
Simultaneous rising trigger at i_bReset and i_bProcessControl
in state 8001H.
Simultaneous rising trigger at i_bReset and i_bProcessControl
in state 8003H.
Description, output setting
The FB is not active. (initial state)
All outputs are set to OFF.
• o_bReady: OFF
• o_bS_OutControl: OFF
• o_bError: OFF
The FB activation startup inhibit is active.
• o_bReady: ON
• o_bS_OutControl: OFF
• o_bError: OFF
Triggered safety FB. Safety outputs are disabled.
i_bS_SafeControl=OFF
• o_bReady: ON
• o_bS_OutControl: OFF
• o_bError: OFF
Safety function startup inhibit is active.
• o_bReady: ON
• o_bS_OutControl: OFF
• o_bError: OFF
Process control is not active and safety is disabled.
• o_bReady: ON
• o_bS_OutControl: OFF
• o_bError: OFF
Process control is active and safety is enabled.
• o_bReady: ON
• o_bS_OutControl: ON
• o_bError: OFF
Action
Set i_bReset to OFF.
Check the devices and wiring of i_bReset.
Set i_bProcessControl to OFF.
Check the setting of i_bStaticControl.
Set i_bReset to OFF.
Check the independence between
i_bProcessControl and i_bReset.
Action
Initialize the FB by setting i_bActivate to ON.
i_bReset required.
i_bS_SafeControl required.
i_bReset required.
i_bProcessControl required.
None.