Muting conditions (forward direction)
No.
State transition
1
8000H→8011H
8000H→8311H
2
8011H→8012H
8311H→8012H
3
8000H→8012H
4
8012H→8021H
24
8012H→8014H
8012H→8314H
25
8014H→8021H
8314H→8021H
5
8021H→8000H
Condition/action
MS_11 is the first entry switch actuated:
Start timers i_dMaxMutingTime and i_dDiscTime11_12.
i_bMutingEnable=ON AND MS_11=OFF→ON AND MS_12=OFF AND MS_21=OFF AND MS_22=OFF
MS_12 is the first entry switch actuated:
Start timers i_dMaxMutingTime and i_dDiscTime11_12.
i_bMutingEnable=ON AND MS_11=OFF AND MS_12=OFF→ON AND MS_21=OFF AND MS_22=OFF
MS_12 is the second entry switch actuated:
Stop timer i_dDiscTime11_12.
i_bMutingEnable=ON AND MS_11=ON AND MS_12=OFF→ON AND MS_21=OFF AND MS_22=OFF
MS_11 is the second entry switch actuated:
Stop timer i_dDiscTime11_12.
i_bMutingEnable=ON AND MS_11=OFF→ON AND MS_12=ON AND MS_21=OFF AND MS_22=OFF
Both entry switches actuated in the same cycle:
Start timer i_dMaxMutingTime.
i_bMutingEnable=ON AND MS_11=OFF→ON AND MS_12=OFF→ON AND MS_21=OFF AND MS_22=OFF
All switches actuated:
MS_11=ON AND MS_12=ON AND MS_21=ON AND MS_22=ON
MS_21 is the first exit switch actuated:
Start timer i_dDiscTime21_22.
MS_11=ON AND MS_12=ON AND MS_21=OFF→ON AND MS_22=OFF
MS_22 is the first exit switch actuated:
Start timer i_dDiscTime21_22.
MS_11=ON AND MS_12=ON AND MS_21=OFF AND MS_22=OFF→ON
MS_22 is the second exit switch actuated:
Stop timer i_dDiscTime21_22.
MS_11=ON AND MS_12=ON AND MS_21=ON AND MS_22=OFF→ON
MS_21 is the second exit switch actuated:
Stop timer i_dDiscTime21_22.
MS_11=ON AND MS_12=ON AND MS_21=OFF→ON AND MS_22=ON
One of the exit switches released:
Stop timer i_dMaxMutingTime.
MS_11=OFF AND MS_12=OFF AND (MS_21=ON→OFF OR MS_22=ON→OFF)
4 SAFETY FB SPECIFICATIONS
4.11 M+SF_MUTEP_R
4
71