Mitsubishi Electric MELSEC iQ-R Series Safety Function Block Reference page 103

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Application example
An application example of M+SF_TSSEN_R is shown below.
■ Labels
• Input labels
Variable name
Allocated device/label
i_bActivate
SA\M100
i_bS_OSSD_In
SA\X1000
i_bStartTest
StartTest (standard/safety shared label)
i_dTestTime
K15
i_bNoExternalTest
SA\X1003
i_bS_StartReset
SA\X1004
i_bS_AutoReset
SA\X1005
i_bReset
SA\X1006
• Output labels
Variable name
Allocated device/label
o_bReady
SA\M200
o_bS_OSSD_Out
SA\Y1001
o_bS_TestOut
SA\Y1002
o_bTestPossible
SA\Y1003
o_bTestExecuted
SA\Y1004
o_bError
SA\Y1005
o_wDiagCode
SA\D1000
Description
Activation of the safety FB
Light curtain output signal
Start test switch (standard control input)
Test time of safety sensor
Manual sensor test status
Reset method for the activated safety FB
Reset method for the input signal reset to ON
Reset switch
Description
Status of whether the safety FB is activated or not.
Light curtain safety demand considering the test
Automatic sensor test request
Possibility of an automatic test
Result of an automatic test
Error flag
Diagnostic code
4 SAFETY FB SPECIFICATIONS
101
4.14 M+SF_TSSEN_R