4.3

M+SF_EDM_R

Overview
Item
Description
Function name
External device monitor
Functional overview
This FB monitors connected actuators such as safety contactors and safety relays (contactors and relays with force-guided contacts)
and controls outputs.
Symbol
(1)
B: i_bActivate
(2)
B: i_bS_OutControl
(3)
B: i_bS_EDM1
(4)
B: i_bS_EDM2
(5)
D: i_dMonitoringTime
(6)
B: i_bS_StartReset
(7)
B: i_bReset
Labels
■ Input labels
No.
Variable name
Data type
(1)
i_bActivate
Bit
(2)
i_bS_OutControl
Bit*
(3)
i_bS_EDM1
Bit*
(4)
i_bS_EDM2
Bit*
(5)
i_dMonitoringTime
Double word
[signed]
(6)
i_bS_StartReset
Bit*
(7)
i_bReset
Bit
M+SF_EDM_R
o_bReady: B
o_bS_EDM_Out: B
o_bError: B
o_wDiagCode: W
Default value
Description
OFF
Activation of the safety FB.
For details, see the following.
Page 11 General Functions
OFF
Control signal from the preceding safety FBs.
Typical function block signals from the library (e.g., M+SF_ESTOP_R,
M+SF_ESPE_R, and/or others).
OFF: Disable safety output (o_bS_EDM_Out).
ON: Enable safety output (o_bS_EDM_Out).
OFF
Feedback signal of the first connected actuator. (NC contact)
OFF: Feedback signals are set to OFF.
ON: Feedback signals are set to ON.
OFF
Feedback signal of the second connected actuator. (NC contact)
OFF: Feedback signals are set to OFF.
ON: Feedback signals are set to ON.
0
Maximum permissible time (in increments of 10ms) from the status of whether
o_bS_EDM_Out is ON or OFF until when i_bS_EDM1 and i_bS_EDM2 are set to ON
or OFF correctly.
Range: Fixed values from 0 to 60000 (0 to 600000ms = 10min)
OFF
Selection of a reset method for the activated (first time) safety FB.
For details, see the following.
Page 11 General Functions
OFF
Reset input.
For details, see the following.
Page 11 General Functions
(8)
(9)
(10)
(11)
4 SAFETY FB SPECIFICATIONS
4.3 M+SF_EDM_R
4
23